Q: How to monitor (digital) sensor communication

A: To check or monitor digital sensor communication, enable the debug mode when connected to the data logger with YdocTerminal.

Enter the following command sequence:

<Cntrl>a  <Shift>d   <Cntrl>d

T: After debugging, the same command sequence disables debug mode.

T: Real-time debugging ASCII sensors is not possible.

Enable raw-value saving to the SD card. After testing download the data file and check results.

Option [6], Log raw data string.

Change from [0], “Off” to [1], “On”.