Take two measurements on one sensor?

Q: We have sometimes a failing SDI-12 sensor reading, the second reading always succeeds.

Is it possible to perform  two readings, ignoring the first one?

(The sensor has a warm-up time of 5 seconds).

A: Yes, that can be done.

  • Set the warm-up time to  to 6 seconds.
  • Create a second SDI-12 driver for the same sensor, with no warm-up and sample time of 5 seconds.
  • Disable data logging for the first, dummy parameter reading.
  • Set both drivers to “Concurrent” Measurement. 

So when waking up 6 seconds before data log interval, the dummy driver starts measurement 5 seconds before data log interval. This measurement will be ignored. The (second) measurement on data log interval will be stored in the data log file.

T: You might have to play with the timing.