Q: We have sometimes a failing SDI-12 sensor reading, the second reading always succeeds.
Is it possible to perform two readings, ignoring the first one?
(The sensor has a warm-up time of 5 seconds).
A: Yes, that can be done.
- Set the warm-up time to to 6 seconds.
- Create a second SDI-12 driver for the same sensor, with no warm-up and sample time of 5 seconds.
- Disable data logging for the first, dummy parameter reading.
- Set both drivers to “Concurrent” Measurement.
So when waking up 6 seconds before data log interval, the dummy driver starts measurement 5 seconds before data log interval. This measurement will be ignored. The (second) measurement on data log interval will be stored in the data log file.
T: You might have to play with the timing.